User Guide Revision 1.12
H2 drive upper speed Staging threshold. When the drive output increases beyond this threshold the next Staging pump is switch on.
The Pump staging settle time must then expire before additional staging pumps can be brought on or off line. Priority for Staging
pump switch on is always given to the pump with lowest run time accumulated.
H2 drive lower speed Staging threshold. When the drive output decreases below this threshold one of the Staging pumps currently
operating is switch off. The Pump staging settle time must then expire before additional staging pumps can be brought on or off line.
Priority for Staging pump switch off is always given to the pump with highest run time accumulated.
Parameter sets a time delay for pump staging whereby, following switch in or switch out of a staging pump, further pumps are not
permitted to be switched in or out until this time period has elapsed. This parameter should be set to allow adequate settle time
between staging pump transitions.
Master drive in pump staging monitors and maintains duty run times for all available staging pumps. All clocks are available to view in
P0-20. P8-20 provides the master reset to all run time clocks used for Pump Staging Function (all clocks set to 0).
For full detail of Pump Staging function configuration see section 7.1 and 7.2, or contact your local drive distributor
-
11.8. Parameter Group 9 – Advance drive control logic configuration
Menu group 9 parameters are detailed in the following Reference Table. They can be accessed through the drive keypad by setting advanced
security level access (P1-14 = 201) or through the OptiTools Studio software suite. Care should be taken in adjusting these parameters. Please
contact your local distributor for further assistance.
Defines the source of the signal to be used for the Enable input
Defines the source of the signal to be used for the Fast Stop input
Defines the source of the signal to be used for the Forward Run input
Defines the source of the signal to be used for the Reverse Run input
Latch function enable control for the run signals (P9-03 and P9-04)
Defines the source of the signal to be used for Reverse run direction control
Defines the source of the signal to be used for the Reset input
External Trip Input Source
Defines the source of the signal to be used for the External trip input
Terminal Control Override Source
Defines the source of the signal to be used for the terminal control override
Defines the Reference Value used for Speed Source 1
Defines the Reference Value used for Speed Source 2
Defines the Reference Value used for Speed Source 3
Defines the Reference Value used for Speed Source 4
Defines the Reference Value used for Speed Source 5
Defines the Reference Value used for Speed Source 6
Defines the Reference Value used for Speed Source 7
Defines the Reference Value used for Speed Source 8
Preset Speed Select Input 0
Preset speed selection multiplex input 0
Preset Speed Select Input 1
Preset speed selection multiplex input 1
Preset Speed Select Input 2
Preset speed selection multiplex input 2
Remote Up Button Input Source
Defines the source of the signal to be used as the Remote UP button
Remote Down Button Input Source
Defines the source of the signal to be used as the Remote DOWN button
Fire mode trigger input selection
Defines the source of the signal to be used for the Fire mode input
Analog Output 1 Control Source
This parameter specifies the relay output 1 control source
Analog Output 2 Control Source
This parameter specifies the relay output 2 control source
This parameter specifies the relay output 1 control source
This parameter specifies the relay output 2 control source
This parameter specifies the scaling control source
PID Reference Source Control
This parameter specifies the PID reference source
PID Feedback Source Control
This parameter specifies the PID feedback source
Relay outputs 3, 4, 5 Function Select
Defines the function of Extended I/O relay outputs 3, 4 and 5
Clean Trigger Input (Edge)
Defines the source of the signal to be used for the pump clean enable input
Defines the source of the signal to be used for the Bypass function enable input
PID 2nd Digital Reference Select Input
Defines the source of the signal to be used for selecting the 2nd digital reference for PID